Temperatures and Flows
TEMPERATURE AND FLOWS
(English Units)
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls ofce for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest Johnson Controls ofce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°F)
COOLER
3
FLOW
(GPM)
AIR ON CONDENSER (°F)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
60 HZ
0157(S/P) 40 60 140 675 0 125
0157(E/V) 40 60 160 750 0 125
0177(S/P) 40 60 160 750 0 125
0177(E/V) 40 60 160 750 0 125
0187(S/P) 40 60 160 750 0 125
0187(E/V) 40 60 160 750 0 125
0197(E/V) 40 60 180 750 0 125
0207(S/P) 40 60 180 800 0 125
0207(E/V) 40 60 180 750 0 125
0227(S/P) 40 60 180 800 0 125
0227(E/V) 40 60 180 750 0 125
0247(S/P) 40 60 180 800 0 125
0247(E/V) 40 60 180 800 0 125
0267(S/P) 40 60 180 800 0 125
0267(E/V) 40 60 250 1200 0 125
0287(S/P) 40 60 250 1200 0 125
0287(E/V) 40 60
250 1200 0 125
0307(S/P) 40 60 300 1200 0 125
0327(E/V) 40 60 300 1200 0 125
0357(S/P) 40 60 300 1200 0 125
0357(E/V) 40 60 300 1200 0 125
0397(S/P) 40 60 300 1200 0 125
0457(P) 40 60 400 1400 0 125