YORK INTERNATIONAL
64
LOCAL DISPLAY READ-OUT
Oper Data
The OPER DATA key also allows the user to scroll
through additional real time display information about
the chiller system which is not available from the DIS-
PLAY keys. This information covers a wide range of
data which includes fan status, loading status, liquid
line solenoid status, run time, etc. A total of 31 different
displays are offered.
When the OPER DATA key is pressed, the following
message will appear:
Repetitively pressing the ENTER key allows the opera-
tor to scroll through the 20 available displays.
In the information that follows, a sample message along
with an explanation of its meaning is provided for all 20
messages.
This message provides a real time display of the time
left on the Load Timer. The Load Timer is a constantly
recycling timer that the micro utilizes in conjunction with
rate control and temperature deviation from setpoint
to determine when loading should occur. The timer will
always start at 150 sec.; however, it may count to 0 at
a rate of up to 5 secs per actual second of time.
This message provides a real timer display of the time
left on the Unload Timer. The Unload Timer is a con-
stantly recycling timer that the micro utilizes in conjunc-
tion with rate control and temperature deviation from
setpoint to determine when unloading should occur.
The timer will always start at 150 sec.; however, it may
count to 0 at a rate of up to 5 secs per actual second
of time.
This message informs the operator what stage of maxi-
mum stage of loading the MASTER (SYS 1 & 2) and
SLAVE (SYS 3 & 4) Module should presently be on as a
result of commands from the MASTER Microproces-
sor. This is a coded number and the steps must be de-
coded to be meaningful. This indication of loading may
be different from the actualy loading due to loading /
unloading timers that are not satisfied and preventing
any action or actual mixed leaving water temperature is
satisfied.
A table for decoding the display message is shown below:
STEP:
0: Both Compressors OFF
1: Lead Compr Unloaded, Lag Compr OFF
2: Lead Compr 1 Stage Loading, Lag Compr OFF
3: Lead Compr 2 Stages Loading, Lag Compr OFF
4: Lead Compr 3 Stages Loading, Lag Compr OFF
5: Lead Compr 2 Stages Loading,
Lag Compr Unloaded
6: Lead Compr 1 Stage Loading,
Lag Compr 1 Stage Loading
7. Lead Compr 2 Stages Loading,
Lag Compr 1 Stage Loading
8. Lead Compr 2 Stages Loading,
Lag Compr 2 Stages Loading
9. Lead Compr 3 Stages Loading
Lag Compr 2 Stages Loading
10. Lead Compr 3 Stages Loading,
Lag Compr 3 Stages Loading
PRESS ENTER TO
DISPLAY DATA
LOAD T I MER
140 SECS
UNLOAD T I MER
122 SECS
MASTER MAX LOAD = 6
S LAVE MAX LOAD = 0
MASTER ACT LOAD = 5
S LAVE ACT LOAD = 0
This message informs the operator what stage of load-
ing the MASTER (SYS 1 & 2) and SLAVE (SYS 3 & 4)
Module is actually on at any given time. This is a coded
number and the steps must be decoded to be mean-
ingful. A table for decoding the display follows:
STEP:
0: Both Compressors OFF
1: Lead Compr Unloaded, Lag Compr OFF
2: Lead Compr 1 Stage Loading, Lag Compr OFF
3: Lead Compr 2 Stages Loading, Lag Compr OFF
4: Lead Compr 3 Stages Loading, Lag Compr OFF
5: Lead Compr 2 Stages Loading,
Lag Compr Unloaded
6: Lead Compr 1 Stage Loading,
Lag Compr 1 Stage Loading
7. Lead Compr 2 Stages Loading,
Lag Compr 1 Stage Loading
8. Lead Compr 2 Stages Loading,
Lag Compr 2 Stages Loading
9. Lead Compr 3 Stages Loading
Lag Compr 2 Stages Loading
10. Lead Compr 3 Stages Loading,
Lag Compr 3 Stages Loading
* On some STEPS actual loading will NOT change due to the
steps not being present on the compressor.