FORM 150.75-NM2
9
YORK INTERNATIONAL
DIMENSIONS
CAUTION
FAILURE TO HEED FOLLOWING RECOMMENDED CLEARANCES MAY RESULT IN REDUCED SYSTEM
PERFORMANCE, NUISANCE SHUTDOWNS, AND SERVICE PROBLEMS.
LD01912
NOTES:
1. Clearances  Minimum YORK required clearances to prevent condenser air recirculation and faulty operation of units are as follows:
Side to wall 8'0"* Rear to wall 8'0"* Control Panel End to wall 5'0"* Top 50'0" Distance between adjacent units 12'
0"
* No more than one wall can be higher than the top of the unit. The aread within the claearnaces shown above and area under the unit
must be kept clear of all obstructions that would impede free air flow to the unit. In installations where winter operation is intended and
snow accumilations are expected, additional unit height must be provided to insure full air flow.
2. Cooler liquid connection sizes (inlet and outlet) 8" victaulic for the YDAJ87KU6  YDAJ99MW9.
3. Dimensions are in inches. Drawings are not to scale and are for planning purposes only. Contact nearest YORK office for detail drawings.
4. Modeules have 1-1/8" of space between to facilitate maintenance.
5. Spring isolators (OPTIONAL) will increase overall height of unit by approx. 6". Refer to FORM 150.40-ES3 for details.
6. Be sure to review WARNINGS on page 2 prior to installation.
WEIGHT DISTRIBUTION (LB.) DIM.
MODEL YDA A B C D E F G H J
J87HU7 1953 1992 2010 2285 1947 2129 2147 2228 1'6"
J87KU6 1954 1995 2013 2287 1956 2141 2159 2236 1'5"
J97KU7 1971 2018 2034 2312 2023 2235 2251 2317 1'6"
J88MU6, J98MU7 1973 2020 2036 2314 2030 2245 2261 2324 1'6-1/2"
J99MW6, J99MU7 2094 2141 2157 2440 2113 2328 2370 2418 1'6-1/2"
J99MW9 2162 2209 2225 2508 2181 2397 2439 2486 1'6-1/2"