Table 108: Programmable
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Winding Setup Service JCI Service
Not shown when Winding Temperature Protection Setpoint on Motor
Details screen is set to Disabled. Allows a Service Technician to program
the High Winding Temperature (266°F to 320°F; default 311°F) and
Winding Hotspot Allowance (0°F to 18°F; default 0°F) safety shutdown
thresholds. Values entered are displayed in the respective data boxes.
Vibration Gain Admin Admin
Only shown when access level is Admin and Motor Vibration Protection
Setpoint on Motor Details screen is not set to Disabled. Allows a Service
Technician to enter values for vibration Input Gain (1:1, 11:1, 21:1
[default]).
Bearing Setup Service JCI Service
Not shown when Bearing Temperature Protection Setpoint on Motor
Details screen is set to Disabled. Allows a Service Technician to enter
values for High Bearing Temperature Shutdown (149°F to 212°F; default
203°F) and Warning (140°F to 194°F; default 194°F) thresholds.
Temperature
Disable
Admin Admin
Only shown when access level is Admin and Winding Temperature
Protection Setpoint on Motor Details screen is not set to Disabled. Allows
a Service Technician to disable individual winding temperature sensors.
The respective temperature data box reflects enabled or disabled status.
This could be applied to defective sensors or for service reasons. When a
sensor is disabled, the respective temperature data box does not appear
on the Motor Details screen.
Table 109: Navigation
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Home Service JCI Service Returns the user to Home screen.
Motor Details Service JCI Service Returns the user to Motor Details screen.
113Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center