Master slot numbers list
Table 172: Master slots numbers list for use with Trend feature
Slot
number
Description Slot
number
Description
256 System: Chiller State 2573 LCSSS: Phase B Current
257 System: Coastdown Time Remaining 2574 LCSSS: Phase C Current
258 System: Prelube Time Remaining 2575 LCSSS: Phase A Voltage
259 System: Are Safety Shutdown Contacts Closed 2576 LCSSS: Phase B Voltage
260 System: Are Cycling Shutdown Contacts Closed 2577 LCSSS: Phase C Voltage
261 System: Are Anticipatory Alarm Contacts Closed 2578 LCSSS: Phase A Temperature
262 System: Operating Hours 2579 LCSSS: Phase B Temperature
263 System: Run Time (in seconds) 2580 LCSSS: Phase C Temperature
264 System: Number of Starts 2581 LCSSS: Starter Model
265 System: Is Stop Switch Closed 2582 LCSSS: Full Load Amps
266 System: Is Start Switch Closed 2583 LCSSS: Voltage Range
267 System: Is Remote Ready to Start 2584 LCSSS: Starting Current
280 External Contact: Is Remote Stop Closed 2585 LCSSS: Is Serial Communications OK
281 External Contact: Is Remote Start Closed 2586 LCSSS: Panel to Sss Comm Errors
282 External Contact: Is MultiUnit Cycling Closed 2587 LCSSS: Sss to Panel Comm Errors
283 External Contact: Is Remote Cycling Closed 2816 VSD: Motor HP
284 External Contact: Is Auxiliary Safety Open 2817 VSD: 100% Full Load Amps
285 Jumper: Is Anti-Recycle Enabled 2818 VSD: Input Power
286 Jumper: Coastdown Operation 2819 VSD: Kilowatt Hours
287 Jumper: Is Diagnostics Enabled 2820 VSD: DC Bus Voltage
288 Jumper: Liquid Type 2821 VSD: DC Inverter Link Current
289 Jumper: Chilled Liquid Pump Operation 2822 VSD: Output Frequency
290 Jumper: Motor Type 2823 VSD: Output Voltage
291 Jumper: Power Failure Restart 2824 VSD: Phase A Current
292 Jumper: Pre- Run Operation 2825 VSD: Phase B Current
293 Jumper: Refrigerant Selection 2826 VSD: Phase C Current
294 Jumper: VSD Motor Supply Line Frequency 2827 VSD: Is Precharge Relay On
295 Jumper: Oil Pump Package 2828 VSD: Is Trigger SCR On
304 Options: Control Mode 2829 VSD: Is Water Pump On
305 Options: System Language 2830 VSD: Control Mode
306 Options: Chiller ID Number 2831 VSD: Command Frequency
307 Options: Display Mode 2832 VSD: Manual Frequency Increment
336 Security: Log In Level 2833 VSD: Internal Ambient Temperature
337 Security: Log In User ID 2834 VSD: Converter Heatsink Temperature
512 Sched: Is Schedule Enabled 2835 VSD: Phase A Heatsink Temperature
1280 Pre- Rotation Vanes: Is Motor Switch Closed 2836 VSD: Phase B Heatsink Temperature
1281 Pre- Rotation Vanes: Position 2837 VSD: Phase C Heatsink Temperature
1282 Pre- Rotation Vanes: Are Vanes Opening 2838 VSD: Is Communications OK
1283 Pre- Rotation Vanes: Are Vanes Closing 2839 VSD: Panel to ACC Comms Error Count
1284 Pre- Rotation Vanes: Are Vanes Holding 2840 VSD: ACC to Panel Comms Error Count
1285 Pre- Rotation Vanes: Control Mode 2841 VSD: ACC to VSD Comms Error Count
1296 Discharge: Temperature 2842 VSD: VSD to ACC Comms Error Count
1536 Oil: Differential Pressure 2843 VSD: VSD to Filter Comms Error Count
1537 Oil: Sump Temperature 2844 VSD: Filter to ACC Comms Error Count
1538 Oil Pump: Control Mode 2845 ACC: Delta P/P
1539 Oil Pump: Is Pump On 2846 ACC: Stability Limit
1540 Oil Pump: Manual Time Left 2847 ACC: Surge Margin
1541 Oil Heater: Is Control Enabled 2848 ACC: Manual Surge Command
1542 Oil Heater: Is Heater On 2849 ACC: Surge Map Count
1543 Oil Return Solenoid: Is Solenoid On 2850 ACC: Surge Type
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center162