JOHNSON CONTROLS
FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
SECTION 5 – TECHNICAL DATA
55
DIMENSIONS - YLAA0300HE,YLAA0360SE, YLAA0400SE (ENGLISH)
TOP VIEW
5/8" DIA MOUNTING
HOLES(TYP)
ORIGIN
(2) RIGGING HOLES
EACH SIDE
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
RIGHT VIEW
FRONT VIEW
B
B
2261
2242 BASE WIDTH
780
TO CLR CONN
2977
193
2077
79
525
14012
VIEW B-B
BOTOM OF PANEL
POWER ENTRY
8712 WIDE X 178 HIGH
28 (TYP)
1086
2393
3613
473
588
588
981
2X 381
6"
(WATER OUTLET)
6"
(WATER
INLET)
Y
C
G
X
FIG. 43 DIMENSIONS (ENGLISH) YLAA0300HE,YLAA0360SE, YLAA0400SE
NOTE:
Placement on a level surface of free of obstructions
(including snow, for winter operation) or air circulation
ensures rated performance, reliable operation, and ease
of maintenance. Site restrictions may compromise
minimum clearances indicated below, resulting in
unpredictable airow patterns and possible diminished
performance. Johnson Controls’s unit controls will
optimize operation without nuisance high-pressure
safety cutouts; however, the system designer must
consider potential performance degradation. Access to
the unit control center assumes the unit is no higher than
on spring isolators. Recommended minimum clearances:
Side to wall – 6'; rear to wall – 6'; control panel to end
wall – 4'0''; top – no obstructions allowed; distance
between adjacent units – 10'. No more than one adjacent
wall may be higher than the unit.