EasyManua.ls Logo

York YLAA0300HE - HEAT EXCHANGER FLOW, GPM

York YLAA0300HE
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
46
FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
SECTION 5 – TECHNICAL DATA
Note: Water Pressure Drop Curves may extend past the minimum and maximum water ow ranges.
HEAT EXCHANGER FLOW, GPM
TABLE 3 – ETHYLENE & PROPYLENE GLYCOL CORRECTION FACTORS
ETHYLENE GLYCOL
% WEIGHT
TONS
kW
COMPR
GPM°F/
TON
PRESS
DROP
FREEZE PT
10 0.985 0.997 24.1 1.034 26
20 0.981 0.996 24.9 1.062 16
30 0.974 0.995 26.1 1.096 5
40 0.966 0.991 27.5 1.134 -10
50 0.957 0.989 29.1 1.172 -32
PROPYLENE GLYCOL
% WEIGHT
TONS
kW
COMPR
GPM°F/
TON
PRESS
DROP
FREEZE PT
10 0.983 0.996 24.2 1.048 27
20 0.974 0.995 24.4 1.086 19
30 0.961 0.990 25.1 1.134 8
40 0.946 0.98 26.0 1.186 -5
50 0.928 0.984 27.2 1.247 -25
CURVE MODEL YLAA
A 240SE, 195HE, 220HE
B 320SE, 360SE, 260HE, 300HE
C 400SE, 435SE, 350HE, 455HE
D 485SE, 440HE
E 390HE, 515HE
1
10
10 0
10 00
1 10 10 0
P res su re D ro p (kP
a)
Wa ter Flow R ate (l/s )
Y L AA E vap o ra to r P ress u re D rop (S I U n its)
A
B
D
C
E

Table of Contents