York YLAA0300HE - Liquid & Refrigerant Sensor Test Points; Table 25 - Entering;Leaving Chilled Liquid Temp. Sensor, Temperature;Voltage Correlation

York YLAA0300HE
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
182
FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
SECTION 9 – SERVICE AND TROUBLESHOOTING
Liquid & Refrigerant Sensor Test Points
(Table 25)
Entering Chilled Liquid Sensor
J6-5 = +5VDC regulated supply to sensor.
J6-8 = VDC input signal to the I/O board. See
Table 25 for voltage readings that correspond
to specic liquid temperatures.
J6-2 = drain (shield connection = 0VDC) Return
Leaving Chilled Liquid Temperature Sensor
J6-4 = +5VDC regulated supply to sensor.
J6-7 = VDC input signal to the microboard. See
Table 25 for voltage readings that correspond
to specic liquid temperatures.
J6-1 = drain (shield connection = 0VDC) Return
TABLE 25 – ENTERING/LEAVING CHILLED LIQUID
TEMP. SENSOR, TEMPERATURE/
VOLTAGE CORRELATION
TEMP °F
VOLTAGE
(Signal Input
to Return)
TEMP °C
10 1.33 -12
12 1.39 -11
14 1.46 -10
16 1.51 -9
18 1.58 -8
20 1.65 -7
22 1.71 -6
24 1.78 -4
26 1.85 -3
28 1.91 -2
30 1.98 -1
32 2.05 0
34 2.12 1
36 2.19 2
38 2.26 3
40 2.33 4
42 2.40 6
44 2.47 7
46 2.53 8
48 2.60 9
50 2.65 10
52 2.73 11
54 2.80 12
56 2.86 13
58 2.92 14
60 2.98 16
62 3.05 17
64 3.11 18
66 3.17 19
68 3.23 20
70 3.29 21
72 3.34 22
74 3.39 23
76 3.45 24
78 3.5 26
80 3.54 27