EasyManua.ls Logo

York YLAA0300HE - SEISMIC ISOLATOR CROSS-REFERENCE

York YLAA0300HE
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
126
FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
SECTION 5 – TECHNICAL DATA
Y2RS
VMC PART NUMBER VMC ISOL. COLOR WEIGHT RANGE (LBS) WEIGHT RANGE (KGS)
Y2RSI-2D-460 GREEN Up thru 391 UP TO 177
Y2RSI-2D-460 GREEN Up thru 391 UP TO 177
Y2RSI-2D-710 DARK BROWN 392 thru 604 178 - 274
Y2RSI-2D-870 RED 605 thru 740 275 - 336
Y2RSI-2D-1200N RED/BLACK 741 thru 1020 337 - 463
Y2RSI-2D-1690 PINK 1021 thru 1437 464 - 652
Y2RSI-2D-2640N PINK/GRAY 1438 thru 2244 653 - 1018
Y2RSI-2D-2870N PINK/GRAY/ORANGE 2245 thru 2618 1019 - 1188
Y2RSI-2D-3280N PINK/GRAY/DK.BROWN 2619 thru 3740 1189 - 1696
SEISMIC ISOLATOR CROSS-REFERENCE
LD13761A
12"
5"
2-3/4"
12-1/4"
8-3/8"
OPER.
HEIGHT
14"
5/8"
3/8"
Ø3/4"
TYP.(4)
3-1/2"
5/8-11UNC
TYP. (4)
2-3/4"
3/4"
7/8"
1-1/8"
3/8" GAP
5"
1/2" LIMIT
STOP &
NUT
NOTES:
1. ALL DIMENSIONS ARE IN INCHES, INTERPRET PER ANSI Y14.
2. STANDARD FINISH: HOUSING-POWDER COATED (COLOR:BLACK), SPRING-POWDER COATED (COLOR: SEE T
HARDWARE ZINC-ELECTROPLATE.
3. EQUIPMENT MUST BE BOLTED OR WELDED TO THE TOP PLATE TO MEET ALLOWABLE SEISMIC RATINGS.
4. ALL SPRINGS ARE DESIGNED FOR 50% OVERLOAD CAPACITY WITH EXCEPTION OF THE 2D-3280N & 2D-2870
5. REFER TO PAGE FOR INSTALLATION INSTRUCTIONS.
6. CONSULT FACTORY FOR CONCRETE INSTALLATION.
REFER TO NEXT PAGE FOR INSTALLATION INSTRUCTIONS
FIG. 54 – SEISMIC ISOLATOR CROSS-REFERENCE

Table of Contents