9JOHNSON CONTROLS
FORM 160.80-EG1 (808)
time period control over four hours, and verication of
time remaining in pulldown cycle from display readout.
Separate digital setpoint for current limiting between
30 and 100%.
The ELECTRO-MECHANICAL STARTER (E–M) screen
displays a picture of the starter and the following values.
The ones below are common among both offerings and the
values will be displayed on both types of starter screens.
From this screen you can perform the following:
Display Only:
Motor Run (LED)
Motor Current % Full Load Amps
Current Limit Setpoints
Pulldown Demand Time Left
Programmable:
Local Motor Current Limit
Pulldown Demand Limit
Pulldown Demand Time
The SOLID STATE STARTER (SSS) screen displays a
picture of the starter and the following values, which are
displayed in addition to the common ones listed above.
From this screen, you can perform the following:
Display Only:
Input Power
kW Hours
Starter Model
Voltage – Phase A, B, C
Current – Phase A, B, C
Temperature – Phase A, B, C
Programmable:
Full Load Amps
Voltage Range
Starting Current
Open SCR
Shorted SCR
kWH Reset
The SETPOINTS screen provides a convenient location
for programming the most common setpoints involved
in the chiller control. The Setpoints are shown on other
individual screens, but to cut down on needless search-
ing, they can all be found on this screen. This screen also
serves as a gateway to a sub-screen for dening the setup
of general system parameters. From this screen you can
perform the following:
Display Only:
Leaving Chilled Liquid Temperature – Setpoint
Leaving Chilled Liquid Temperature Cycling –
Shutdown
Leaving Chilled Liquid Temperature Cycling –
Restart
Current Limit Setpoint
Programmable:
Local Leaving Chilled Liquid Temperature – Range
Local Leaving Chilled Liquid Temperature – Setpoint
Leaving Chilled Liquid Temperature Cycling Offset –
Shutdown
Leaving Chilled Liquid Temperature Cycling Offset –
Restart
Remote Analog Input Range
Local Motor Current Limit
Pulldown Demand Limit
Pulldown Demand Time
Print
The SETUP is the top level of the general congura-
tion parameters. It allows programming of the time and
date, along with specications as to how the time will be
displayed. In addition, the chiller conguration as deter-
mined by the micro board program jumpers and program
switches is displayed. From this screen you can perform
the following:
Display Only:
Chilled Liquid Pump Operation (Displays Standard or
Enhanced)
Refrigerant Selection (Displays R-22 or R-134a)
Anti-Recycle (Displays Disabled or Enabled)
Power Failure Restart (Displays Manual or Auto-
matic)
Liquid Type (Displays Water or Brine)
Programmable:
Set Date
Set Time
Clock (Enabled/Disabled)
12/24 Hour