EasyManuals Logo

Zenner zelsius C5-ISF Installation And Operating Instructions

Zenner zelsius C5-ISF
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
20
Programming of M-Bus address
(optional)
Select of the display „Adr 000“ in
level 3 (same for the additional
inputs Adr1to Adr3).
Press the button for about 2
seconds (until the door symbol
reappears) and then release. The
right digit starts ashing. With
one short push the value of the
digit is incremented.
With each long press, the selected
value will be taken over and
change to next digit (as soon as
desired character ashes, release
the button).
If the desired value is reached,
you have to press the button
until the number stops ashing
and the return to the menu is
completed. Now the new value is
programmed.
The programming process can be
repeated if necessary.
Note: If the editor is not terminated,
maybe changed values are being
saved aer the automatic return to
the main display.
Radio (optional)
General information
zelsius®-energy meters which have
an integrated radio interface with an
antenna are marked for better visibil-
ity on the upper cover with one of the
following symbols:
wM-Bus
®
colour connection signication
white I/O 1 In-/Output 1
yellow I/O 2 In-/Output 2
green I/O 3 In-/Output 3
brown GND
common ground
for I/O 1-3
Technical data I/O
Load max. 30V DC/ 20 mA
I/O 1, 2, 3
Open Drain, n-channel
FET
Cable D = 3.8 mm, 4-wire
Pulse-duty
factor
1:1 (out); 1:5 (in)
Cable length 1.5 m
Input fre-
quency
max. 1 Hz
M-Bus (optional)
The optional M-Bus interface com-
plies with standard EN 1434-3 and
operates with 2400 baud xed. The
two conductors can be connected in
any order to the M-Bus network.
A rmly attached cable is included,
external wiring must be done by
oneself.
Technical data M-Bus
Cable length 1.5 m
Cable D = 3.8 mm, 2-wire
colour connection signication
brown M-Bus 1 M-Bus-cable 1
white M-Bus 2 M-Bus-cable 2
All manuals and user guides at all-guides.com

Table of Contents

Other manuals for Zenner zelsius C5-ISF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Zenner zelsius C5-ISF and is the answer not in the manual?

Zenner zelsius C5-ISF Specifications

General IconGeneral
BrandZenner
Modelzelsius C5-ISF
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals