LOOP 500
10
5. Disable / enable operations
Disabling and re-enabling is possible as from the 2nd level.
5.1 Disabling and enabling zones and detectors
Disabling a detector
To disable a detector (e.g. No.12), the following keys should be pressed:
OFFZone
1
*
1
2
Steps carried out appear as follows on the display:
Z o n e X X X M l d Y Y O F F L 2 *
Execution of the command is shown on the display as follows:
D i s a b l e Z o n e X X X M l d Y Y T T T T T T T T T T T T L 2 *
Disable - indicates that disable has been carried out
TTT.. - possible customer text (for detector No.12)
Indications
the DISABLE collective display illuminates
if operation of the control panel is disabled again by the key switch, the DISABLE LED will continue to be
actuated
Enabling a detector
In order to enable a detector (e.g. No.12) of a zone (e.g. No.1), the following keys should be pressed:
OFFZone
1
*
1
2
Steps carried out are shown on the display as follows:
Z o n e _ _ 1 M l d 1 2 O N L 2 *
Execution of the command is shown on the display as follows:
D i s a b l e E n d Z o n e 0 0 1 M l d 1 2 T T T T T T T T T T T T L 2 *
Dis. end - indicates that a disable operation has been terminated
TTT.. - possible customer text (for detector No.12)
the DISABLE collective display only extinguishes when no further Disable is present in the control panel