LOOP 500
10
5. Disable / enable operations
Disabling and re-enabling is possible as from the 2nd level.
5.1 Disabling and enabling zones and detectors
Disabling a detector
To disable a detector (e.g. No.12), the following keys should be pressed:
OFFZone
1
*
1
2
Steps carried out appear as follows on the display:
Z o n e X X X M l d Y Y O F F L 2 *
Execution of the command is shown on the display as follows:
D i s a b l e Z o n e X X X M l d Y Y T T T T T T T T T T T T L 2 *
Disable - indicates that disable has been carried out
TTT.. - possible customer text (for detector No.12)
Indications
−
the DISABLE collective display illuminates
−
if operation of the control panel is disabled again by the key switch, the DISABLE LED will continue to be
actuated
Enabling a detector
In order to enable a detector (e.g. No.12) of a zone (e.g. No.1), the following keys should be pressed:
OFFZone
1
*
1
2
Steps carried out are shown on the display as follows:
Z o n e _ _ 1 M l d 1 2 O N L 2 *
Execution of the command is shown on the display as follows:
D i s a b l e E n d Z o n e 0 0 1 M l d 1 2 T T T T T T T T T T T T L 2 *
Dis. end - indicates that a disable operation has been terminated
TTT.. - possible customer text (for detector No.12)
−
the DISABLE collective display only extinguishes when no further Disable is present in the control panel