3. Operation on the 2nd operator control level
3.1. Accessing the 2nd operator control level
In order to access the 2nd operator control level, it will be necessary to use the key switch in the control and
indicating unit.
a) enabling second operator control level
insert the key in the key switch and turn towards OPERATION ENABLE
the display illumination will switch on
the ACCESS LED will illuminate
the transmission unit will be disabled
the DISABLE LED and FAULT/DISABLE LED in the MASTER CONTROL PANEL field will illuminate
apart from the Inspection ON and Inspection OFF keys, all the keys integrated in the control and
indicating unit are operational
b) disabling second operator level
turn the key towards OPERATION DISABLED and withdraw
the display illumination will switch off
the transmission unit will switch on automatically if not disabled from the control and indicating unit
keyboard
the DISABLE LED and FAULT/DISABLE LED in the MASTER CONTROL PANEL extinguish if there is
no further reason for their activation
c) available controls on the second operator control level
On this operator control level it is possible to cancel all faults and fire alarms provided that the
cause is cleared
The following further controls are available on the second operator control level:
Disabling/enabling zones and detectors
Disabling/enabling controls, deactivating and activating
Disabling/enabling alarm devices, deactivating and activating
Disabling/enabling the transmission unit
Resetting pre alarms
Trigger emergency alarms
Carry out the day / night mode setting
Indicate the event memory and programm version via special functions
accessing the third operator control level (code)