LOOP 500
11
Disabling a zone
To disable a zone (e.g. No.2), the following keys should be pressed:
OFF
Zone
2
*
Enabling a zone
To enable a zone, the following keys should be pressed:
ONZone
2
*
By disabling individual detectors of a zone, it is possible to disable the entire zone. The individual Disable
operations are indicated as disabling of a detector; disabling of the last detector is indicated as disabling the
zone.
If only part of a zone is disabled (e.g. 8 of 20 detectors), these can be re-enabled individually, or the entire
zone can be enabled, which means the same thing in principle.
5.2. Disabling/enabling, deactivating and activating controls
5.2.1. Disabling/enabling controls
Disabling a control
The following keys should be pressed to disable a control (e.g. No.2):
OFFControl
2
Steps carried out are shown on the display as follows:
C o n t r o l _ _ 2 O F F L 2 *
Execution of the command is shown as follows on the display:
D i s a b l e C o n t r o l 0 0 2 T T T T T T T T T T T T L 2 *
Disable - indicates that a Disable operation has been carried out
TTT.. - possible customer text (for Control No.2)
Indications
the DISABLE collective display illuminates
if operation of the control panel is disabled again by the key switch, the DISABLE LED will continue to be
actuated
http://www.firealarmengineers.com