Chapter11PeripheralDeviceInstallation
Steps
1.Connectoneendofthenetworkcabletothenetworkinterfaceofthealarmbox,and
thenconnecttheotherendtotheportofthehubortothelayer-2switchthatresides
inthesameLANwiththealarmserver.
2.PerformthefollowingprocedurestoconnecttheDCpowercabletothepowersupply
terminalofthealarmbox.
a.Connecttheblackwiretothe–48VRTNterminalofthepowersupply.
b.Connectthebluewiretothe–48Vterminal.
c.Tightenthewireswiththein-builtscrews.
Note:
Bothwiresmustberespectivelyconnectedtotheterminalofthesametypeatboth
ends.
3.SelecteitherofthefollowingcableroutingmethodstoinstallthePVCcabletrunking
onthewallinaccordancewiththeinstallationplaceofthealarmbox.
OptionDescription
ToproutingMountthePVCcabletrunkingalongthewalltothecableladdersothatthe
cablescanberoutedalongthecableladderandthenintothecabinet.
BottomroutingMountthePVCcabletrunkingalongthewalltotheoorsothatthecables
canberoutedalongthecabletrayundertheoorandthenintothecabinet.
4.RoutethepowercableandthenetworkcableintothePVCcabletrunking,andthen
installthecoverplateofthecabletrunking.
–EndofSteps–
11-7
SJ-20141121113158-006|2014-12-20(R1.0)ZTEProprietaryandCondential