EasyManuals Logo

AAON SS1063 User Manual

AAON SS1063
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
VAV/ZONE CONFIGURATION
VCC-X Operator Interface SD
72
VAV/Zone Con guration Screens
VAV/Zone Con guration
In order to correctly set up the VAV/Zone Controller, you must rst
con gure several parameters in regard to the type of system and
operating parameters for the VAV/Zone Controller you have installed.
Most of these values and operating parameters are only set once at
the initial system setup and are never changed.
Modular Service Tool Instructions
From any Menu Screen, press the <CONFIGURATION> button. The
Unit Selection Screen, shown below, will appear requesting that you
enter the unit ID number.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the correct unit ID number of the VAV/Zone controller you
want to con gure, and press <ENTER>. Once communication is
established, “No Communication” will be replaced with “Press
Down.” Then
press <>. You will then see Unit Con guration Screen
#1
. Press <ENTER> to save entered data and press <> to scroll
through the screens.
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
System Manager SD Instructions
From any Main screen, press <SETPOINTS>. The screen below
will appear because this option requires passcode clearance. Only a
Level 2 passcode can change setpoints.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will
be displayed.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the Unit ID of the controller you want to con gure and press
<ENTER>. Once communication is established, “No Communica-
tion” will be replaced with “Press Down.”
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
The following screen will be displayed:
Change Setpoints
Configure Unit
Save/Copy/Restore
Scroll down to the ‘Con gure Unit’ option and press <ENTER>.
This will take you to the rst Con guration Screen shown below.
Con guration Screen #1 - Box Con guration
XX Box Cnfg IDXXXX
Box Configuration
COOLING ONLY BOX
Use < Or > To Change
This Box Control Code will operate in one of four possible modes.
The box designation will display on the top line of all screens.
0 = COOLING ONLY BOX (will display as CO Box)
1 = H/C CHANGEOVER BOX (will display as HC Box)
2 = SERIES FAN BOX (will display as SF Box)
3 = PARALLEL FAN BOX (will display as PF Box)
Con guration Screen #2 - Damper Operation
XX Box Cnfg IDXXXX
Damper Operating
Mode: DIRECT ACTING
Use < Or > To Change
Select Direct Acting or Reverse Acting. If the damper opens in a
clockwise direction, it is DIRECT ACTING. If the damper opens in
a counter-clockwise direction, it is REVERSE ACTING.
CAUTION: If you change this setting, you MUST cycle
power to the controller to allow it to re-calibrate
the damper feedback positions for its new
direction of control!

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AAON SS1063 and is the answer not in the manual?

AAON SS1063 Specifications

General IconGeneral
BrandAAON
ModelSS1063
CategoryController
LanguageEnglish

Related product manuals