EasyManua.ls Logo

AAON V3 Series - Figure 9 - Apply Gasket; Figure 10 - Connect Sections; Figure 11 - Bar Clamp

AAON V3 Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
Control Box
Some V3 units include an external control
box that must be mounted in the field. The
control box is designed with two mounting
holes on the back panel. Make sure the wall
fasteners can hold the weight of the control
box. See Figure 14.
External control boxes provided with
conduit exceeding 1.8 m (6ft) in length must
have conduit supported in compliance with
the National Electrical Code NFPA 70.
FMC and LMFC conduit must be supported
within 30.5 cm (12 in.) of both the unit and
the external control box and at intervals no
more than 1.4 m (4.5 ft) along the length.
Figure 14 - Back View External Control
Box
Electrical
Verify the unit nameplate agrees with power supply. Connect power and control field wiring as
shown on the unit specific wiring diagram provided laminated and attached to the door in the
controls compartment.
Table 4 - Nameplate Voltage Markings & Tolerances
Hz
Nameplate
Voltage
Nominal
System
Voltage
Operating Voltage Range
1
Acceptable Performance
Range
2
Min
Max
Min
Max
60
115
120
104
127
108
126
208/230
208/240
187
254
187
252
208
208
187
228
187
228
230
240
208
254
216
252
265
277
240
293
249
291
460
480
416
508
432
504
575
600
520
635
540
630
50
230
230
198
254
208
254
400
400
344
440
360
440
Notes:
1. Operating voltage is the min and max voltage for which the unit can function. Never
operate outside of this min and max voltage.
2. The Acceptable Performance Range is the min and max voltage for which the unit
performance is designed and rated to give acceptable performance.

Table of Contents