AAON V3 Series - Options; Heating Coils; Table 10 - Steam Distributing Coil Sweat Connection Sizes; Figure 21 - Steam Distributing Piping

AAON V3 Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
Table 12 - Chilled Water Coil Sweat
Connection Sizes
Model (V3-)
Supply and Return
Connection Size (OD)
A
2.9 cm
1 1/8"
B
3.5 cm
1 3/8"
C
4.1 cm
1 5/8"
D
5.4 cm
2 1/8”
E
5.4 cm
2 1/8”
Connect the chilled water supply to the
bottom of the coil and return to the top.
Water supply lines must be insulated with
closed cell type pipe insulation or insulation
that includes a vapor barrier. Lines must be
properly fastened, drained and supported
according to local code requirements, and job
specifications.
Table 13 - Minimum and Maximum Coil
Pressures and Temperatures
Direct Expansion (DX) Systems
All DX refrigerant coils are factory charged
with a nitrogen holding charge. All DX
systems include evaporator coils and thermal
expansion valves (TXV).
Never turn off the main power supply to the
unit, except for servicing, emergency, or
complete shutdown of the unit. When power
is cut off from the unit, crankcase heaters
cannot prevent refrigerant migration into the
split system condensing unit compressors.
This means the compressor may cool down
and liquid refrigerant may accumulate in the
compressor. The compressor is designed to
pump refrigerant gas and damage may occur
when power is restored.
Chilled Water
Hot Water
Min. Entering
Air
15.6°C (60°F)
4.4 °C (40°F)
Max Entering
Air
37.8°C (100°F)
26.7°C (80°F)
Min. Entering
Water
1.7°C (35°F)
60°C (140°F)
Max Entering
Water
18.3°C (65°F)
93.3°C (200°F)
Min. Water
Pressure
0 kpa (15 psig)
Max Water
Pressure
2068kpa (300 psig)
Piping shall be in accordance with
national and local codes. Pressure
limiting devices, backflow preventers
and all other safety requirements are
the sole responsibility of the installing
contractor.
WARNING
Ensure water piping entries into the
unit are properly sealed. Failure to
seal the entries may result in damage
to the unit and property.
CAUTION
CRANKCASE HEATER
OPERATION
Some units are equipped with
compressor crankcase heaters, which
must be energized at least 24 hours
prior to cooling operation, to clear any
liquid refrigerant from the
compressors.
CAUTION