EasyManua.ls Logo

ABB 2600T Series - Level Measurement

ABB 2600T Series
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 13 -
PHASE 4 - TRANSMITTER OPERATION
5.2 LEVEL MEASUREMENT
1. Vent all entrapped air from primary using vent/drain valves
on the transmitter, then close them.
2. Make sure to have the level in the tank at the required
reference (minimum) level
.
Note - In case it is not possible to empty the tank, it is
possible to follow the Zero Raise/Lower adjustment
procedure described in the reference manual.
3. After venting, the output should be 4 mA dc. If not:
a. Rotate the nameplate to get access to the external push
buttons.
b. Push the zero (Z) button on top of the transmitter (fig. 5.2)
for at least 2 seconds.
c. The output goes to 4 mA, and if present the integral
display, the message "ZERO PASS" will appear.
d. If a "WRITE DISABLE" message appears on the integral
display, check the dip switches settings (you need to
open the cover on the electronic side and to pull out the
integral display: see fig. 5.1).
e. In case of other diagnostic messages, see the reference
manual.
Min. Level
Max. Level
gate valve
Max. Level
Min. Level

Other manuals for ABB 2600T Series

Related product manuals