EasyManua.ls Logo

ABB AC 31 - Page 140

ABB AC 31
221 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming
ABB Control - AC 31 Page 5-31
1SBC 260400 R1001-b 06.99
Filtering time
0 : internal filter according to the documentation of analog extension
1-127 : integration number
192 : 60Hz Filter
224 : 50Hz Filter
All channels of one extension will be affected by this parameter.
The time filter formula is
K=FILT0
Vn= result (T)
Vn-1=result (T-1)
Vins=analog value without filtering
Vn=
Σn/ K
With Σn=(Vins –Vn-1) + Σn-1
Initial value is : V1=Vins
Σ1=K V1
WARNING: The second extension XM06B5 connected to a remote unit can not be configured
by the user program.
Only one analog extension can be configured on a remote unit.

Table of Contents