Controller configuration via terminal program Section 7 Commissioning
102 M&I – AC 900F Controller
Auto restore
The controller can be configured to automatically restore the configuration data
saved on the SD card (Backup config) when a cold start is initiated. For more
information on this function refer to Section 8, Service.
Diagnostic interface transmission rate
The Diagnostic interface transmission rate can be set to 9600 Bit/s or 19200 Bit/s.
Default value is 19200 Bit/s.
Waiting time for the configuration block start-up
Any value between 2 and 60 seconds can be entered for the waiting time. In case of
an invalid entry, the boot loader repeats this configuration item. It is recommended
not to change the default setting.
The boot loader then displays the current configuration data that are still to be saved.
Auto restore from SD card [n]
Enter baudrate of console port: [19200]
Enter CPU delay (in seconds) before starting up: [2]
The default setting for all other parameters must not be changed!