Section 7 Commissioning Controller configuration via terminal program
M&I – AC 900F Controller 101
ETH2
Enter [5] to enable the redundancy link at ETH2 for operation of a redundant
controller. The IP address, baud rate and mode for the application are defined as
default settings.
ETH3
Select [6] to configure the controller for the connection to a redundant Control Net.
ETH3 will then operate with the setting 10/100 MBit auto.
ETH4
Set Ethernet link 2 configuration:
0. Auto negotiation
1. 100 MBit full duplex
2. 100 MBit half duplex
3. 10 MBit full duplex
4. 10 MBit half duplex
5. Redundancy Link
7. Offline
Select: [5]
Set Ethernet link 3 configuration:
0. 10/100 MBit auto
6. Redundant ControlNet
7. Offline
Select: [7]
Set Ethernet link 4 configuration:
0. 10/100 MBit auto
7. Offline
Select: [7]