E-Clipse Bypass Configurations for ACH550 Drives 51
Parameter Descriptions
Group 03
Code Name Resolution Range Default Description
0301 FBUS CW 1 b0: 1 = Start
b1: 1 = Fault reset
b2: 1 = Run disable
b3: 1 = Field bus local
b4: 1 = Start disable 1
b5: 1 = Start disable 2
b6: 1 = Start disable 3
b7: 1 = Start disable 4
b8: 1 = Bypass override
b9: 1 = Link On
b10 - b15: not used
0 Control word 1 from field bus
0303 FBUS SW 1 b0: 1 = Ready
b1: 1 = Enabled
b2: 1 = Started
b3: 1 = Running
b4: 1 = Field bus local
b5: 1 = Fault
b6: 1 = Alarm
b7: 1 = Notice
b8: 1 = Request control
b9: 1 = Override
b10: 1 = Powered up
b11: 1 = Bypass mode
b12: 1 = Panel local mode
b13 - 15: not used
0 Status word 1 to field bus
0305 FLT WORD 1 b0: 1 = Coil current
measurement
b1: 1 = Bypass contact
stuck
b2: 1 = Drive contact stuck
b3: 1 = Bypass coil open
b4: 1 = Drive coil open
b5: 1 = Undervoltage
b6: not used
b7: 1 = Drive AI2 fault
b8: 1 = Motor overload
b9: 1 = Input phase A loss
b10: 1 = Input phase B loss
b11:1 = Input phase C loss
12: 1 = Drive 1st start fault
b13: 1 = coil power supply
fault
b14: not used
b15: 1 = Earth fault
0 Bypass fault status, word 1