62 E-Clipse Bypass Configurations for ACH550 Drives
Parameter Descriptions
Group 32
Code Name Resolution Range Default Description
3206 FBK LOSS 1 0 = BYP STOP
1 = BYP START
BYP
START
(1)
Bypass contactor operation if
drive link fault, drive AI2 loss or
excessive cycling.
Group 33
Code Name Resolution Range Default Description
3301 FW
VERSION
hex — Revision of main application
firmware.
3302 PT VERSION hex — Revision of panel text file.
3303 LP VERSION — — Loading package version.
3304 CB VERSION — — Control board version.
3305 TEST DATE — —
3306 DRIVE TYPE — — Drive Type - copy of drive's
parameter 33.04.
3307 SUB
ASMBLY
— — Bypass Sub assembly type.
3308 PLANT
CODE
1 0-9 0 Part of bypass serial number:
Shows 1 digit plant code.
Identifies the factory where the
device was made
3309 MFG
DATE
1 0107 - 5299 0 Part of bypass serial number:
Shows 4 digit manufacturing
date. WWYY. (2 digits for the
week number 01-52 and 2 digits
for the year)
3310 UNIT
NUM
1 00001 - 65535 0 Part of bypass serial number:
Shows 5 digit unit number here.
Tell sorder number of a unit
manufactured during a certain
week. Maximum number is
65525.
Group 50
Code Name Resolution Range Default Description
5001 BP PROT ID hex 0x0000 - 0xFFFF 0x0000 Group 50 shall mimic Group 53
except settings shall apply to
bypass node.
5002 BP MAC ID 1 0 - 65535 2 Bypass station ID (NODE
ADDRESS)
5003 BAUD RATE 0.1 kbit/s 1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6, 76.8
9.6 Read-only copy from Group 53.