E-Clipse Bypass Configurations for ACH550 Drives 63
Parameter Descriptions
Group 50
Code Name Resolution Range Default Description
5004 EFB PARITY 1 0=8 NONE 1,
1=8 NONE 2,
2=8 EVEN 1,
3=8 ODD 1
0 Read-only copy from Group 53.
5005 PROFILE 1 0=ABB DRV LIM,
1=DCU PROFILE,
2=ABB DRV FULL
0 Read-only copy from Group 53.
5006 BP OK MSG 1 0 - 65535 0
5007 BP CRC ERR 1 0 - 65535 0
5008 UART
ERROR
1 0 - 65535 0 Read-only copy from Group 53.
5009 BP STATUS 1 0=IDLE,
1=EXECUT INIT,
2=TIME OUT,
3=CONFIG ERR,
4=OFF-LINE,
5=ON-LINE,
6=RESET,
7=LISTEN ONLY
0
5010
...
5018
BP PAR 10
...
BP PAR 18
1 0 - 65535 0
5019
...
5020
BP PAR 19
...
BP PAR 20
hex 0x0000 - 0xFFFF 0x0000
5021
...
5022
BP PAR 21
...
BP PAR 22
1/256 kWh 1/256 kWh - 8388608 kWh 0 kWh 32 bit number representing
energy saved (parameter 0114)
by using drive.
Calculated: Drive savings (kWh)
= (65536 x (parameter 5021 +
parameter 5022)) / 256.
Group 51
Code Name Resolution Range Default Description
5101 FBA TYPE 1 0 = NOT DEFINED
1 = Profibus
15 = LonWorks
32 = CANOpen
37 = DeviceNet
— Displays type of attached
fieldbus adapter module.
5102
...
5126
FBA PAR 2
...
FBA PAR 26
1 0 - 65535 0 Fieldbus specific - consult FBA
User’s Manual.
5127 REFRESH 1 0 = DONE
1 = REFRESH
0 Validates any changed adapter
module configuration
parameters. After refreshing,
value reverts automatically to
DONE.