E-Clipse Bypass Configurations for ACH550 Drives 65
Parameter Descriptions
Group 53
Code Name Resolution Range Default Description
5319
...
5320
DV PAR 19
...
DV PAR 20
hex 0x0000 - 0xFFFF 0x0000
Group 54
Code Name Resolution Range Default Description
5401
...
5409
DATA IN 1
...
DATA IN 9
1 0 = Not In Use
1 = Control Word (ABBDP)
2 = Ref 1 (ABBDP)
3 = Ref 2 (ABBDP)
4 = Status Word (ABBDP)
5 = Actual Value 1
(ABBDP)
6 = Actual Value 2
(ABBDP)
10001 - 19999 = Bypass
parameter index
+10000
Figure module support. Specifies
addresses of parameters to be
read from the drive (IN to
network). Only for modules that
support the cyclic low scanner
function.
Group 55
Code Name Resolution Range Default Description
5501
...
5510
DATA OUT 1
...
DATA OUT10
1 0 = Not In Use
1 = Control Word (ABBDP)
2 = Ref 1 (ABBDP)
3 = Ref 2 (ABBDP)
4 = Status Word (ABBDP)
5 = Actual Value 1
(ABBDP)
6 = Actual Value 2
(ABBDP)
10001 - 19999 = Bypass
parameter index
+10000
Figure module support. Specifies
addresses of parameters to be
read from the drive (OUT to
network). Only for modules that
support the cyclic low scanner
function.
Group 98
Code Name Resolution Range Default Description
9802 COMM PROT
SEL
1 0=NOT SEL
1=STD MODBUS
2=N2
3=FLN
4=EXT FBA
5=BACNET
0 This parameter functions in place
of drive parameter 98.02 which
must be set to Modbus in E-
Clipse Bypass system. User
fieldbus is set at E-Clipse panel.
Group 99
Code Name Resolution Range Default Description
9902 B.P. MACRO 1 1 = HVAC DEFAULT
2 = DAMPER
3 = RETROFIT
4 = SMOKE CONTROL
1 Select bypass macro. Predifined
set of parameter values for
certain application is loaded in
use.