E-Clipse Bypass Configurations for ACH550 Drives 91
Technical Data
Vertical Enclosure Terminals, 500…600 Volt Units
Standard Enclosure Terminals, 208…240 Volt Units,
500…600 Volt
Frame
Size
Maximum Wire Size Capacities of Power Terminals
HP Identification
Circuit
Breaker
Disconnect
Switch
Motor
Termination
Ground
Lugs
2 ACH550-VxR-02A7-6 R2
#8
62 in-lbs
#8
7 in-lbs
#6
30 in-lbs
#4
35 in-lbs
3 ACH550-VxR-03A9-6 R2
5 ACH550-VxR-06A1-6 R2
7.5 ACH550-VxR-09A0-6 R2
10 ACH550-VxR-011A-6 R2
15 ACH550-VxR-017A-6 R2
20 ACH550-VxR-022A-6 R3
#4
62 in-lbs
#2
50 in-lbs
#2
50 in-lbs
25 ACH550-VxR-027A-6 R3
30 ACH550-VxR-032A-6 R4
#1
62 in-lbs
#4
18 in-lbs
#2/0
120 in-lbs
40 ACH550-VxR-041A-6 R4
50 ACH550-VxR-052A-6 R4
#1
55 in-lbs
60 ACH550-VxR-062A-6 R4
#1
70 in-lbs
208…240 Volt
Frame
Size
Maximum Wire Size Capacities of Power Terminals
HP Identification
Circuit
Breaker
Disconnect
Switch
Motor
Termination
Ground Lugs
1 ACH550-BxR-04A6-2 R1
#8
40 in-lbs
#8
7 in-lbs
#6
30 in-lbs
#4
35 in-lbs
1.5 ACH550-BxR-06A6-2 R1
2 ACH550-BxR-07A5-2 R1
3 ACH550-BxR-012A-2 R1
5 ACH550-BxR-017A-2 R1
7.5 ACH550-BxR-024A-2 R2
10 ACH550-BxR-031A-2 R2/R3
#1
50 in-lbs
#2
50 in-lbs
#2
50 in-lbs
15 ACH550-BxR-046A-2 R3
#4
18 in-lbs
#2
120 in-lbs
20 ACH550-BxR-059A-2 R3
25 ACH550-BxR-075A-2 R4
#1
55 in-lbs

Table of Contents