32 EN – R6…R9 Quick installation guide
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Ensure the cooling
See table I on page 27 (UL: table II on page 27) for the heat dissipation. The
maximum ambient temperature is 40 C (+104 °F). No condensation or frost is
allowed. For more information on the ambient temperature, see chapter Technical
data in ACH580-01 hardware manual (3AUA0000076331 [English]).
Protect the drive and input power cable
See tables III, IV and V on pages 28 and 29 for the fuses.
If you use gG fuses, make sure that the operating time of the fuse is below
0.5 seconds. Follow the local regulations.
Install the drive on the wall
Warning! The drive module is heavy (45 to 98 kg / 99 to 216 lb). Use a suitable
lifting device. Do not lift the module manually. Make sure that the wall and the
fixing devices can carry the weight.
See figure R6…R9 Figures A on page 41.