Miniature circuit breaker
FrameACS180-04...
ABB type
S203P-B50R3-25A0-4
S203P-B63R3-033A-4
S803S-B80R4-038A-4
S803-B100R4-045A-4
S803-B100R4-050A-4
■
Manual self-protected combination motor controller – Type E USA
(UL (NEC))
You can use the ABB Type E manual motor protectors (MMP) MS132 & S1-M3-25,
MS165-xx and MS5100-100 as an alternative to the recommended fuses as a means
of branch circuit protection. This is in accordance with the National Electrical Code
(NEC). When the correct ABB Type E manual motor protector is selected from the
table and used for branch circuit protection, the drive is suitable for use in a circuit
capable of delivering no more than 65 kA rms symmetrical amperes at the maximum
rated voltage of the drive. See the table below for the appropriate MMP types and
minimum enclosure volume of IP20 / UL open type drive mounted in an enclosure.
If you use a manual motor protector for the branch circuit protection of the drive,
install the drive into a metal enclosure.
Note: The UL Listing of drive and MMP combinations applies only to drives that
are mounted in appropriately sized metal enclosures that are capable of containing
any drive component failure.
Minimum enclosure volume
4)
MMP type
1) 2) 3)
Frame
Type ACS180-
04...
in
3
dm
3
1-phase
U
n
= 200…240 V
89015
MS132-6.3 & S1-M3-25
5)
R002A4-1
89015
MS132-10 & S1-M3-25
5)
R003A7-1
89015
MS132-10 & S1-M3-25
5)
R004A8-1
89015.3MS165-16R106A9-1
89015MS165-20R107A8-1
89015MS165-25R109A8-1
97016MS165-32R212A2-1
3-phase
U
n
= 200…240 V
89015
MS132-6.3 & S1-M3-25
5)
R002A4-2
89015
MS132-10 & S1-M3-25
5)
R003A7-2
89015
MS132-10 & S1-M3-25
5)
R004A8-2
89015MS165-16R106A9-2
89015MS165-20R107A8-2
106 Technical data