FrameAWG
Cable conductor sizes (mm
2
)
1)
ACS180-04...
R2143×2.5 + 2.5-12A6-4
R2103×6 + 6-17A0-4
R3103×6 + 6-25A0-4
R383×10 + 10-033A-4
R483×10 + 10-038A-4
R463x16 + 16-045A-4
R443×25 + 16-050A-4
1)
Size of typical power cable (symmetrical, shielded, three-phase copper cable). Note that for the input
power connection, you may have to use two separate PE conductors (IEC 61800-5-1).
Terminal data for the control cables
TorqueWire size
lbf·inN·mAWGmm
2
n/an/a22 - 160.5 - 1.5
External EMC filters
The table shows the external EMC filters. See also EMC compatibility and motor
cable length and Technical data (page 91).
EMC filter typeACS180-
04...
Schaffner order codeABB order code
1-phase
U
n
= 200 ... 240 V
FS 21754-16.1-07RFI-1202A4-1
FS 21754-16.1-07RFI-1203A7-1
FS 21754-16.1-07RFI-1204A8-1
FS 21754-16.1-07RFI-1206A9-1
FS 21754-16.1-07RFI-1207A8-1
Contact ABBContact ABB09A8-1
Contact ABBContact ABB12A2-1
3-phase
U
n
= 200 ... 240 V
FS43566-16-44RFI-31102A4-2
FS43566-16-44RFI-31103A7-2
FS43566-16-44RFI-31104A8-2
FS43566-16-44RFI-31106A9-2
FS43566-16-44RFI-31107A8-2
FS43566-16-44RFI-31109A8-2
FS43566-30-33RFI-32115A6-2
FS43566-30-33RFI-32117A5-2
FN 3258-30-33RFI-3325A0-2
114 Technical data