ABB ACS180 - Recommended Maintenance Intervals after Start-Up; Cleaning the Heatsink

ABB ACS180
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Recommended maintenance intervals after start-up
Recommended annual actions by the user
Connections and environment
PQuality of the supply voltage
Spare parts
ISpare parts
PReforming DC circuit capacitors of spare modules
Inspections
ITightness of terminals
IDustiness, corrosion and temperature
PCleaning the heatsink
Years from start-up
Maintenance task/object
21181512963
Cooling fans
RRRMain cooling fan (frames R1...R4)
Note:
Maintenance and component replacement intervals are based on the
assumption that the equipment is operated within the specified ratings and
ambient conditions. ABB recommends annual drive inspections to ensure the
highest reliability and optimum performance.
Long term operation near the specified maximum ratings or ambient conditions
may require shorter maintenance intervals for certain components. Consult
your local ABB Service representative for additional maintenance
recommendations.
Cleaning the heatsink
The drive module heatsink fins pick up dust from the cooling air. The drive runs
into overtemperature warnings and faults if the heatsink is not clean. When
necessary, clean the heatsink as follows.
WARNING!
Use the required personal protective equipment. Wear protective gloves and
long sleeves. Some parts have sharp edges.
80 Maintenance