Loading...
Radiated emissions are according to C2 with single phase ACS180-04S...-1
drives. For ACS180-04S...-4 drives, use a metal enclosure to fulfill radiated
emissions C2/C1 limits with an external EMC filter.
External EMC filter must be used together with ACS180-04S-... drives.
For ACS180-04N... drives, the maximum motor cable lengths are according to
the motor cable length table. The EMC category for these drives is C4.
For ACS180-04S-...-2 drives, the EMC category is C4. In order to achieve higher
EMC category, must use external EMC filters.
Control connection data
0 10 V DC (10% overrange, 11 V DC max.)Voltage signal, single-
ended
Analog inputs (AI1,
AI2)
R
in
= 38 kohm
0 20 mA (10% overrange, 22 mA max.)Current signal, single-
ended
R
in
= 205 ohm
1.0%, of full scaleInaccuracy
10 V DC ±1%, max. load current 10 mAPotentiometer refer-
ence value
0 20 mA (10% overrange, 22 mA max.) into
maximum 500 ohm load
Current output modeAnalog output (AO)
0 10 V DC (10% overrange, 11 V DC max.)
into 200 kohm minimum load (resistive)
Voltage output mode
1.5%, of full scaleInaccuracy
+24 V DC ±10%, max. 100 mAAs outputAuxiliary voltage out-
put (+24V)
12 24 V DC (int. or ext. supply) max. 30 V
DC.
VoltageDigital inputs
(DI1…DI4)
PNP and NPNType
R
in
= 2 kohmInput impedance
As outputsDigital output(DO)
Transistor output PNPType
30 V DCMax. switching
voltage
60 mA / 30 V DC, short-circuit protectedMax. switching cur-
rent
1 form C (NO + NC)TypeRelay output (RA, RB,
RC))
250 V AC / 30 V DCMax. switching
voltage
2 AMax. switching cur-
rent
10 Hz…16 kHzFrequency input
DI3 and DI4 can be used as digital or frequency inputs.(FI)