6
Medium voltage network1
Neighboring network2
Point of measurement3
Low voltage4
Equipment (victim)5
Equipment6
Supply transformer7
Static screen8
Drive9
2. An EMC plan for preventing disturbances is drawn up for the installation. A
template is available from the local ABB representative.
3. The motor and control cables are selected as specified in this manual.
4. The drive is installed according to the instructions given in this manual.
WARNING!
To prevent radio-frequency interference, do not use a category C4 drive on
a low-voltage public network which supplies domestic premises.
WARNING!
You can install a drive with the internal EMC filter connected only on a
symmetrically grounded TN-S system.