ACS510 User’s Manual 53
Start-Up
0125 AO20.0…20.0mA 0.1mA-
0126
PID 1 OUTPUT -1000.0…1000.0% 0.1% -
0127 PID 2 OUTPUT -100.0…100.0% 0.1% -
0128
PID 1 SETPNT Unit and scale defined by par. 4006/
4106 and 4007/4107
--
0129
PID 2 SETPNT Unit and scale defined by par. 4206 and
4207
0130
PID 1 FBK Unit and scale defined by par. 4006/
4106 and 4007/4107
--
0131
PID 2 FBK Unit and scale defined by par. 4206 and
4207
--
0132
PID 1 DEVIATION Unit and scale defined by par. 4006/
4106 and 4007/4107
--
0133
PID 2 DEVIATION Unit and scale defined by par. 4206 and
4207
--
0134
COMM RO WORD 0…65535 1 0
0135
COMM VALUE 1 -32768…+32767 1 0
0136
COMM VALUE 2 -32768…+32767 1 0
0137
PROCESS VAR 1- 1
0138 PROCESS VAR 2- 1
0139
PROCESS VAR 3- 1
0140
RUN TIME 0.00…499.99 kh 0.01 kh 0 kh
0141 MWH COUNTER 0…9999 MWh 1 MWh -
0142
REVOLUTION CNTR 0…65535 Mrev 1 Mrev 0
0143
DRIVE ON TIME HI 0…65535 Days 1 day 0
0144 DRIVE ON TIME LO hh.mm.ss 1 = 2s 0
0145
MOTOR TEMP -10...200 °C/ 0...5000 Ohm / 0…1 1 0
0146…
0148
Not used
0149
OVERRIDE ACTIVED
0..1 1 0
0150
CB TEMP
-20.0 ... 150.0 °C 1.0 °C -
0151
INPUT KWH (R)
0.0 ... 999.9 kWh 1.0 kWh -
0152
INPUT MWH
0 ... 9999 MWh 1 MWh -
0158
PID COMM VALUE 1
-32768 ... +32767 1 -
0159
PID COMM VALUE 2
-32768 ... +32767 1 -
Group 03: FB Actual Signals
0301
FB CMD WORD 1- - -
0302
FB CMD WORD 2- - -
0303
FB STS WORD 1- - -
0304
FB STS WORD 2- 1 0
0305
FAULT WORD 1- 1 0
0306
FAULT WORD 2- 1 0
0307
FAULT WORD 3- 1 0
0308
ALARM WORD 1- 1 0
0309
ALARM WORD 2- 1 0
Group 04: Fault History
0401
LAST FAULT Fault codes (panel displays as text) 1 0
Code Name Range Resolution Default User S
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn