54 ACS510 User’s Manual
Start-Up
0402 FAULT TIME 1 Date dd.mm.yy / power-on time in days 1 day 0
0403
FAULT TIME 2 Time hh.mm.ss 2 s 0
0404 SPEED AT FLT -32768 ... +32767 1 rpm 0
0405
FREQ AT FLT -3276.8 ... +3276.7 0.1 Hz 0
0406
VOLTAGE AT FLT 0.0 ... 6553.5 0.1 V 0
0407 CURRENT AT FLT 0.0 ... 6553.5 0.1 A 0
0408
TORQUE AT FLT -3276.8 ... +3276.7 0.1% 0
0409 STATUS AT FLT 0 ... 0xFFFF (hex) 1 0
0410
DI 1-3 AT FLT 000…111 (0…7 decimal) 1 0
0411
DI 4-6 AT FLT 000…111 (0…7 decimal) 1 0
0412 PREVIOUS FAULT 1 As Par. 0401 1 0
0413
PREVIOUS FAULT 2 As Par. 0401 1 0
Group 10: Start/Stop/Dir
1001
EXT1 COMMANDS 0…10 1 2
+N688:1
+N689:1
9
1002
EXT2 COMMANDS 0…10 1 0 9
1003
(
NOTE)
DIRECTION 1…3 1 3 9
Group 11: Reference Select
1101
KEYPAD REF SEL 1…2 1 1
1102
EXT1/EXT2 SEL -6…8 1 0 9
1103 REF1 SELECT 0…17, 20…21 1 1 9
1104
REF1 MIN 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1Hz 0.0Hz
1105
REF1 MAX 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 50.0 Hz /
+N688:50.0 Hz /
+N689:55.0 Hz
1106
REF2 SELECT 0…17, 19…21 1 2 9
1107
REF2 MIN 0.0…100.0% 0.1% 0.0%
1108
REF2 MAX 0.0…100.0% 0.1% 100.0%
Group 12: Constant Speeds
1201
CONST SPEED SEL -14 …14 1 9 9
1202
CONST SPEED 1 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 5.0 Hz /
+N688:5.0 Hz /
+N689:5.5Hz
1203
CONST SPEED 2 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 10.0 Hz /
+N688:10.0 Hz /
+N689:11.0 Hz
1204
CONST SPEED 3 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 15.0 Hz /
+N688:15.0 Hz /
+N689:16.5Hz
1205
CONST SPEED 4 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 20.0 Hz /
+N688:20.0 Hz /
+N689:22.0 Hz
Code Name Range Resolution Default User S
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn