56 ACS510 User’s Manual
Start-Up
1511 MAXIMUM AO2 0.0…20.0 mA 0.1 mA 20.0 mA
1512
FILTER AO2 0.0…10.0s 0.1s 0.1s
Group 16: System Controls
1601
RUN ENABLE -6…7 1 0 9
1602
PARAMETER LOCK 0…2 1 1
1603 PASS CODE 0…65535 1 0
1604
FAULT RESET sEL -6…8 1 0
1605 USER PAR SET CHG -6…6 1 0
1606
LOCAL LOCK -6…8 1 0
1607
PARAM SAVE 0=DONE, 1 = SAVE 10
1608 START ENABLE 1-6…7 1 0
1609
START ENABLE 2-6…7 1 0
1610
DISPLAY ALARMS 0...1 1 0
Group 17:Override Mode
1701
OVERRIDE SEL -6…6 1 0
1702
OVERRIDE FREQ 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:-0.0...55.0 Hz
0.1Hz 0.0
1704
OVERRIDE PASSCODE 0...65535 1 0
1705
OVERRIDE ENABLE 0...2 1 0
1706
OVERRIDE DIR
-6...7 1 0
1707
OVERRIDE REF
1...2 1 1
Group 20: Limits
2003
MAX CURRENT 0… 1.1 * I
2n
0.1 A 1.1 * I
2n
9
2005 OVERVOLT CTRL 0 = DISABLE, 1 = ENABLE 11
2006
UNDERVOLT CTRL 0 = DISABLE, 1 = ENABLE (TIME),
2 =
ENABLE
11
2007
MINIMUM FREQ -500.0…500.0 Hz /
+N688:-50.0...50.0 Hz /
+N689:-55.0...55.0 Hz
0.1Hz 0.0Hz 9
2008
MAXIMUM FREQ 0…500.0 Hz /
+N688:0...50.0 Hz /
+N689:0...55.0 Hz
0.1 Hz 50.0 Hz /
+N688:50.0 Hz /
+N689:55.0 Hz
9
Group 21: Start/Stop
2101
START FUNCTION 1…5, 8 1 8 9
2102
STOP FUNCTION 1 = COAST, 2 = RAMP 11
2103
DC MAGN TIME 0.00…10.00 s 0.01 s 0.30 s
2104
DC CURR CTL 0, 2 - 0 9
2106
DC CURR REF 0%…100% 1% 30%
2107
DC BRAKE TIME 0.0…250.0 s 0.1 s 0.0 s
2108
START INHIBIT 0=OFF, 1 = ON 10 9
2109
EM STOP SEL -6…6 1 0
2110
TORQ BOOST CURR 15…300% 1% 100%
2113
START DELAY
0.00…60.00 s 0.01 s 0.00 s
Code Name Range Resolution Default User S
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn