60 ACS510 User’s Manual
Start-Up
3705 LOAD TORQ LOW 1 0%...600% 1% 10%
3706
LOAD TORQ HIGH 1 0%...600% 1% 300%
3707 LOAD FREQ 2 0...500 Hz 1 Hz 25 Hz
3708
LOAD TORQ LOW 2 0%...600% 1% 15%
3709
LOAD TORQ HIGH 2 0%...600% 1% 300%
3710 LOAD FREQ 3 0...500 Hz 1 Hz 43 Hz
3711
LOAD TORQ LOW 3 0%...600% 1% 25%
3712 LOAD TORQ HIGH 3 0%...600% 1% 300%
3713
LOAD FREQ 4 0...500 Hz 1 Hz 50 Hz
3714
LOAD TORQ LOW 4 0%...600% 1% 30%
3715 LOAD TORQ HIGH 4 0%...600% 1% 300%
3716
LOAD FREQ 5 0...500 Hz 1 Hz 500 Hz
3717
LOAD TORQ LOW 5 0%...600% 1% 30%
3718
LOAD TORQ HIGH 5 0%...600% 1% 300%
Group 40: Process PID Set 1
4001
GAIN 0.1…100 0.1 2.5
4002 INTEGRATION TIME 0.0s = NOT SEL, 0.1…3600.0 s 0.1 s 3.0 s
4003
DERIVATION TIME 0…10.0s 0.1s 0.0s
4004
PID DERIV FILTER 0…10.0s 0.1s 1.0s
4005 ERROR VALUE INV 0 = NO, 1 = YES -0
4006
UNITS 0…127 1 4
4007
UNIT SCALE 0…4 1 1
4008 0% VALUE Unit and scale defined by par. 4006 and
4007
-0.0%
4009 100%
VALUE Unit and scale defined by par. 4006 and
4007
- 100.0%
4010
SET POINT SEL 0…2, 8...17, 19, 20 1 1 9
4011
INTERNAL SETPNT Unit and scale defined by par. 4006 and
4007
0.1% 40.0%
4012
SETPOINT MIN -500.0%…500.0% 0.1% 0.0%
4013
SETPOINT MAX -500.0%…500.0% 0.1% 100.0%
4014
FBK SEL 1…13 1 1
4015
FBK MULTIPLIER -32.768…32.767 (0 = not used) 0.001 0
4016
ACT1 INPUT 1…7 1 2 9
4017
ACT2 INPUT 1…7 1 2 9
4018
ACT1 MINIMUM -1000…1000% 1% 0%
4019
ACT1 MAXIMUM -1000…1000% 1% 100%
4020
ACT2 MINIMUM -1000…1000% 1% 0%
4021
ACT2 MAXIMUM -1000…1000% 1% 100%
4022
SLEEP SELECTION -6…7 1 0
4023
PID SLEEP LEVEL 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 0.0 Hz
4024
PID SLEEP DELAY 0.0…3600.0 s 0.1 s 60.0 s
4025
WAKE-UP DEV Unit and scale defined by par. 4006 and
4007
-0.0%
Code Name Range Resolution Default User S
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn