ACS510 User’s Manual 61
Start-Up
4026 WAKE-UP DELAY 0…60 s 0.01 s 0.50 s
4027
PID 1 PARAM sET -6…7 1 0
Group 41: Process PID Set 2
4101
GAIN 0.1…100 0.1 2.5
4102
INTEGRATION TIME 0.0s = NOT SEL, 0.1…3600 s 0.1 s 3.0 s
4103 DERIVATION TIME 0.0…10.0 s 0.1 s 0.0 s
4104
PID DERIV FILTER 0.0…10.0 s 0.1 s 1.0 s
4105 ERROR VALUE INV 0 = NO, 1 = YES -0
4106
UNITS 0…127 1 4
4107
UNIT SCALE 0…4 1 1
4108 0% VALUE Unit and scale defined by par. 4106 and
4107
-0.0%
4109 100%
VALUE Unit and scale defined by par. 4106 and
4107
- 100.0%
4110
SET POINT SEL 0…2, 8…17, 19, 20 1 1 9
4111
INTERNAL SETPNT Unit and scale defined by par. 4106 and
4107
0.1% 40.0%
4112
SETPOINT MIN -500.0%…500.0% 0.1% 0.0%
4113
SETPOINT MAX -500.0%…500.0% 0.1% 100.0%
4114 FBK SEL 1…13 1 1
4115
FBK MULTIPLIER -32.768…32.767 (0 = NOT USED) 0.001 0
4116
ACT1 INPUT 1…7 1 2 9
4117 ACT2 INPUT 1…7 1 2 9
4118
ACT1 MINIMUM -1000…1000% 1% 0%
4119
ACT1 MAXIMUM -1000…1000% 1% 100%
4120 ACT2 MINIMUM -1000…1000% 1% 0%
4121
ACT2 MAXIMUM -1000…1000% 1% 100%
4122
SLEEP SELECTION -6…7 1 0
4123 PID SLEEP LEVEL 0.0…500.0 Hz /
+N688:0.0...50.0 Hz /
+N689:0.0...55.0 Hz
0.1 Hz 0.0 Hz
4124
PID SLEEP DELAY 0.0…3600.0 s 0.1 s 60.0 s
4125
WAKE-UP DEV Unit and scale defined by par. 4106 and
4107
-0.0%
4126
WAKE-UP DELAY 0.00…60.00 s 0.01 s 0.50 s
Group 42: Ext / Trim PID
4201
GAIN 0.1…100.0 0.1 1.0
4202
INTEGRATION TIME 0.0s = NOT SEL, 0.1…3600.0 s 0.1 s 60.0 s
4203
DERIVATION TIME 0.0…10.0 s 0.1 s 0.0 s
4204
PID DERIV FILTER 0.0…10.0 s 0.1 s 1.0 s
4205
ERROR VALUE INV 0 = NO, 1 = YES 10
4206
UNITS 0…127 1 4
4207
UNIT SCALE 0…4 1 1
4208 0%
VALUE Unit and scale defined by par. 4206 and
4207
-0%
4209 100%
VALUE Unit and scale defined by par. 4206 and
4207
- 100%
Code Name Range Resolution Default User S
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd