Free space requirements
The flange-mounted drives can be installed side by side. The free space
requirements above and below the drives are shown below. For additional
requirements, refer to sections Examining the installation site (page 13) and
Additional requirements for cabinet installations (page 16).
Note: The free space requirements below are for the heat sink side of the mounting
plate. There is no free space requirement for the front side of the mounting plate.
That area can be occupied by other equipment (e.g., contactors, relays, wires,
ducts, etc.).
BAFrame
inmminmm
7.872003.94100R1 R2
7.872004.53115R3 R5
11.813007.87200R6 R9
Mechanical installation General 15