150 Parameters
10.09 DI3 ON delay Defines the activation delay for digital input DI3. 0.0 s
t
On
= 10.09 DI3 ON delay
t
Off
= 10.10 DI3 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
0.0 3000.0 s Activation delay for DI3. 10 = 1 s
10.10 DI3 OFF delay Defines the deactivation delay for digital input DI3. See
parameter 10.09 DI3 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for DI3. 10 = 1 s
10.11 DI4 ON delay Defines the activation delay for digital input DI4. 0.0 s
t
On
= 10.11 DI4 ON delay
t
Off
= 10.12 DI4 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
0.0 3000.0 s Activation delay for DI4. 10 = 1 s
10.12 DI4 OFF delay Defines the deactivation delay for digital input DI4. See
parameter 10.11 DI4 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for DI4. 10 = 1 s