156 Parameters
11.08 DIO1 OFF delay Defines the deactivation delay for digital input/output DIO1
(when used as a digital output or digital input). See parameter
11.07 DIO1 ON delay.
0.0 s
0.0 … 3000.0 s Deactivation delay for DIO1. 10 = 1 s
11.09 DIO2 function Selects whether DIO2 is used as a digital output or input, or a
frequency output.
Output
Output DIO2 is used as a digital output. 0
Input DIO2 is used as a digital input. 1
Frequency DIO2 is used as a frequency output. 2
11.10 DIO2 output source Selects a drive signal to be connected to digital input/output
DIO2 when parameter 11. 0 9 DIO2 function is set to Output.
For the available selections, see parameter 11.06 DIO1 output
source.
Running
11.11 DIO2 ON delay Defines the activation delay for digital input/output DIO2
(when used as a digital output or digital input).
0.0 s
t
On
= 11.11 DIO2 ON delay
t
Off
= 11.12 DIO2 OFF delay
*Electrical status of DIO (in input mode) or status of selected source (in output mode). Indicated by 11.01 DIO status.
**Indicated by 11.02 DIO delayed status.
0.0 … 3000.0 s Activation delay for DIO2. 10 = 1 s
11.12 DIO2 OFF delay Defines the deactivation delay for digital input/output DIO2
(when used as a digital output or digital input). See parameter
11.11 DIO2 ON delay.
0.0 s
0.0 … 3000.0 s Deactivation delay for DIO2. 10 = 1 s
11.38 Freq in 1 actual
value
Displays the value of frequency input 1 (via DIO1 when it is
used as a frequency input) before scaling. See parameter
11.42 Freq in 1 min.
This parameter is read-only.
-
0 … 16000 Hz Unscaled value of frequency input 1. 1 = 1 Hz
11.39 Freq in 1 scaled Displays the value of frequency input 1 (via DIO1 when it is
used as a frequency input) after scaling. See parameter 11.42
Freq in 1 min.
This parameter is read-only.
-
-32768.000 …
32767.000
Scaled value of frequency input 1. 1 = 1
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
*DIO status
**Delayed DIO status
Time