EasyManua.ls Logo

ABB ACS880-11 - Page 169

ABB ACS880-11
604 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters 169
14.06 DIO delayed status (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Displays the delayed status of the digital input/outputs on the
extension module. This word is updated only after
activation/deactivation delays (if any are specified).
Bit 0 indicates the status of DIO1.
Note: The number of active bits in this parameter depends on
the number of digital input/outputs on the extension module.
Example: 1001b = DIO1 and DIO4 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b Delayed status of digital input/outputs. 1 = 1
14.08 DI filter time (Visible when 14.01 Module 1 type = FDIO-01)
Defines a filtering time for parameters 14.05 DI status and
14.06 DI delayed status.
10.0 ms
0.8 100.0 ms Filtering time for DI status parameters. 10 = 1 ms
14.08 DIO filter time (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Defines a filtering time for parameters 14.05 DIO status and
14.06 DIO delayed status. The filtering time will only affect the
DIOs that are in input mode.
10.0 ms
0.8 100.0 ms Filtering time for DIO status parameters. 10 = 1 ms
14.09 DIO1 function (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Selects whether DIO1 of the extension module is used as a
digital input or output.
Input
Output DIO1 is used as a digital output. 0
Input DIO1 is used as a digital input. 1
14.11 DIO1 output source (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Selects a drive signal to be connected to digital input/output
DIO1 of the extension module when parameter 14.09 DIO1
function is set to Output.
Not
energized
Not energized Output is not energized. 0
Energized Output is energized. 1
Ready run Bit 1 of 06.11 Main status word (see page 131). 2
Enabled Bit 0 of 06.16 Drive status word 1 (see page 132). 4
Started Bit 5 of 06.16 Drive status word 1 (see page 132). 5
Magnetized Bit 1 of 06.17 Drive status word 2 (see page 133). 6
Running Bit 6 of 06.16 Drive status word 1 (see page 132). 7
Ready ref Bit 2 of 06.11 Main status word (see page 131). 8
At setpoint Bit 8 of 06.11 Main status word (see page 131). 9
Reverse Bit 2 of 06.19 Speed control status word (see page 135). 10
Zero speed Bit 0 of 06.19 Speed control status word (see page 135). 11
Above limit Bit 10 of 06.17 Drive status word 2 (see page 133). 12
Warning Bit 7 of 06.11 Main status word (see page 131). 13
Fault Bit 3 of 06.11 Main status word (see page 131). 14
Fault (-1) Inverted bit 3 of 06.11 Main status word (see page 131). 15
Start request Bit 13 of 06.16 Drive status word 1 (see page 132). 16
Open brake
command
Bit 0 of 44.01 Brake control status (see page 328). 22
Ext2 active Bit 11 of 06.16 Drive status word 1 (see page 132). 23
No. Name/Value Description Def/FbEq16