316 Parameters
40.23 Set 1 internal
setpoint 3
Defines process setpoint preset 3. See parameter 40.19 Set 1
internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit selection.
0.00
-32768.00 …
32767.00
Process setpoint preset 3. 1 = 1 unit
40.24 Set 1 internal
setpoint 4
Defines process setpoint preset 4. See parameter 40.19 Set 1
internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit selection.
0.00
-32768.00 …
32767.00
Process setpoint preset 4. 1 = 1 unit
40.25 Set 1 setpoint
selection
Configures the selection between setpoint sources 1 (40.16)
and 2 (40.17).
This parameter is only effective when parameter 40.18 Set 1
setpoint function is set to In1 or In2.
0 = Setpoint source 1
1 = Setpoint source 2
Setpoint
source 1
Setpoint source 1 0. 0
Setpoint source 2 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
Other [bit] Source selection (see Terms and abbreviations on page 114
). -
40.26 Set 1 setpoint min Defines a minimum limit for the process PID controller
setpoint.
0.00
-32768.00 …
32767.00
Minimum limit for process PID controller setpoint. 1 = 1
40.27 Set 1 setpoint max Defines a maximum limit for the process PID controller
setpoint.
32767.00
-32768.00 …
32767.00
Maximum limit for process PID controller setpoint. 1 = 1
40.28 Set 1 setpoint
increase time
Defines the minimum time it takes for the setpoint to increase
from 0% to 100%.
0.0 s
0.0 … 1800.0 s Setpoint increase time. 1 = 1
40.29 Set 1 setpoint
decrease time
Defines the minimum time it takes for the setpoint to decrease
from 100% to 0%.
0.0 s
0.0 … 1800.0 s Setpoint decrease time. 1 = 1