Parameters 413
95.09 Switch fuse
controller
(Only visible with a BCU control unit)
Activates communication to a BSFC charging controller. This
setting is intended for use with inverter modules that are
connected to a DC bus through a DC switch/charging circuit
controlled by a charging controller. On units without a DC
switch, this parameter should be set to Disable.
The charging controller monitors the charging of the inverter
unit, and sends an enable command when the charging has
finished (ie. DC switch is closed after the ‘charging OK’ lamp
lights, and charging switch opened).
For more information, see BSFC documentation.
Enable
Disable Communication with BSFC disabled. 0
Enable Communication with BSFC enabled. 1
95.13 Reduced run mode (Only visible with a BCU control unit)
Specifies the number of inverter modules available.
This parameter must be set if reduced run is required. A value
other than 0 activates the reduced run function.
If the control program cannot detect the number of modules
specified by this parameter, a fault (5695 Reduced run) is
generated.
See section Reduced run function (page 93).
0 = Reduced run disabled
1…12 = Number of modules available
Note: This parameter cannot be changed while the drive is
running.
0
0…65535 Number of inverter modules available -
95.14 Connected modules (Only visible with a BCU control unit)
Shows which of the parallel-connected inverter modules have
been detected by the control program.
-
0000h…FFFFh Inverter modules connected. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Module 1 1 = Module 1 has been detected.
1 Module 2 1 = Module 2 has been detected.
…… …
11 Module 12 1 = Module 12 has been detected.
12…15 Reserved