Parameters 427
96.61 User data logger
status word
Provides status information on the user data logger (see page
499).
This parameter is read-only.
0000b
0000b…1111b User data logger status word. 1 = 1
96.63 User data logger
trigger
Triggers, or selects a source that triggers, the user data
logger.
Off
Off 0. 0
On 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 114). -
96.64 User data logger
start
Starts, or selects a source that starts, the user data logger. Off
Off 0. 0
On 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 114). -
96.65 Factory data logger
time level
Selects the sampling interval for the factory data logger (see
page 498).
500us
500us 500 microseconds. 500
2ms 2 milliseconds. 2000
10ms 10 milliseconds. 10000
96.70 Disable adaptive
program
Disables/enables the adaptive program (if present).
See also section Adaptive programming (page 27).
Note: This parameter cannot be changed while the drive is
running.
No
No Adaptive program enabled. 0
Yes Adaptive program disabled. 1
96.100 Change user pass
code
(Visible when user lock is open)
To change the current user pass code, enter a new code into
this parameter as well as 96.101 Confirm user pass code. A
warning will be active until the new pass code is confirmed. To
cancel changing the pass code, close the user lock without
confirming. To close the lock, enter an invalid pass code in
parameter 96.02 Pass code, activate parameter 96.08 Control
board boot, or cycle the power.
See also section User lock (page 92).
10000000
10000000…
99999999
New user pass code. -
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Running 1 = The user data logger is running. The bit is cleared after the post-trigger
time has passed.
1 Triggered 1 = The user data logger has been triggered. The bit is cleared when the
logger is restarted.
2 Data
available
1 = The user data logger contains data that can be read. Note that the bit is
not cleared because the data is saved to the memory unit.
3 Configured 1 = The user data logger has been configured. Note that the bit is not
cleared because the configuration data is saved to the memory unit.
4…15 Reserved