48 Electrical installation
Checking the insulation of the assembly
See the hardware manual.
Attaching the residual voltage warning sticker
See the hardware manual.
Power cable connection diagram
1 Use a separate grounding PE cable (1a) or a cable with a separate PE conductor (1b)
if the conductivity of the shield does not meet the requirements for the PE conductor.
2 We recommend 360-degree grounding if shielded cable is used. Ground the other end
of the input cable shield or PE conductor at the distribution board.
3 We require 360-degree grounding.
4 Switch-disconnector and fuses. See section Selecting the supply disconnecting device
in the hardware manual.
PE
Drive module
U1
V1
W1
3 ~ M
U2
V2
W2
23
9
8
7
6
L1 L2 L3(PE) (PE)PE
L1 L2 L3
2
1b1a
4
R- R+
UDC- UDC+
5
T1/ T2/ T3/
R- R+ UDC-
UDC+
U2 V2 W2
PE
L1
L2
L3