Parameters 285
32.29 Supervision 3 low Defines the lower limit for signal supervision 3. 0.00
-21474830.00 …
21474830.00
Low limit. -
32.30 Supervision 3 high Defines the upper limit for signal supervision 3. 0.00
-21474830.00 …
21474830.00
Upper limit. -
33
33 Generic timer &
counter
Configuration of maintenance timers/counters.
See also section Maintenance timers and counters (page 88).
33.01 Counter status Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have exceeded
their limits.
This parameter is read-only.
-
0000 0000b …
0011 1111b
Maintenance time/counter status word. 1 = 1
33.10 On-time 1 actual Displays the actual present value of on-time timer 1.
The timer runs whenever the signal selected by parameter
33.13 On-time 1 source is on.
When the timer exceeds the limit set by 33.11 On-time 1 warn
limit, bit 0 of 33.01 Counter status is set to 1. The warning
specified by 33.14 On-time 1 warn message is also given if
enabled by 33.12 On-time 1 function.
The timer can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
-
0…4294967295 s Actual present value of on-time timer 1. -
33.11 On-time 1 warn limit Sets the warning limit for on-time timer 1. 0 s
0…4294967295 s Warning limit for on-time timer 1. -
No. Name/Value Description Def/FbEq16
Bit Name Description
0 On-time1 1 = On-time timer 1 has reached its preset limit.
1 On-time2 1 = On-time timer 2 has reached its preset limit.
2 Edge 1 1 = Signal edge counter 1 has reached its preset limit.
3 Edge 2 1 = Signal edge counter 2 has reached its preset limit.
4 Value 1 1 = Value counter 1 has reached its preset limit.
5 Value 2 1 = Value counter 2 has reached its preset limit.
6…15 Reserved