148 Parameters
07.107 LSU loading
package version
(Only visible when IGBT supply unit control activated by
95.20)
Version number of the loading package of the supply unit
firmware.
-
10
10 Standard DI, RO
Configuration of digital inputs and relay outputs.
10.01 DI status Displays the electrical status of digital inputs DIIL and
DI6…DI1. The activation/deactivation delays of the inputs (if
any are specified) are ignored. A filtering time can be defined
by parameter 10.51 DI filter time.
Bits 0…5 reflect the status of DI1…DI6; bit 15 reflects the
status of the DIIL input. Example: 1000000000010011b =
DIIL, DI5, DI2 and DI1 are on, DI3, DI4 and DI6 are off.
This parameter is read-only.
-
0000h…FFFFh Status of digital inputs. 1 = 1
10.02 DI delayed status Displays the status of digital inputs DIIL and DI6…DI1. This
word is updated only after activation/deactivation delays (if
any are specified). A filtering time can be defined by
parameter 10.51 DI filter time.
Bits 0…5 reflect the delayed status of DI1…DI6; bit 15 reflects
the delayed status of the DIIL input.
This parameter is read-only.
-
0000h…FFFFh Delayed status of digital inputs. 1 = 1
10.03 DI force selection The electrical statuses of the digital inputs can be overridden
for eg. testing purposes. A bit in parameter 10.04 DI force
data is provided for each digital input, and its value is applied
whenever the corresponding bit in this parameter is 1.
0000h
0000h…FFFFh Override selection for digital inputs. 1 = 1
10.04 DI force data Contains the values that the digital inputs are forced to when
selected by 10.03 DI force selection.
Bit 0 is the forced value for DI1; bit 15 is the forced value for
the DIIL input.
0000h
0000h…FFFFh Forced values of digital inputs. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Value
0 1 = Force DI1 to value of bit 0 of parameter 10.04 DI force data.
1 1 = Force DI2 to value of bit 1 of parameter 10.04 DI force data.
2 1 = Force DI3 to value of bit 2 of parameter 10.04 DI force data.
3 1 = Force DI4 to value of bit 3 of parameter 10.04 DI force data.
4 1 = Force DI5 to value of bit 4 of parameter 10.04 DI force data.
5 1 = Force DI6 to value of bit 5 of parameter 10.04 DI force data.
6…14 Reserved
15 1 = Force DIIL to value of bit 15 of parameter 10.04 DI force data.