Parameters 153
10.26 RO1 OFF delay Defines the deactivation delay for relay output RO1. See
parameter 10.25 RO1 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for RO1. 10 = 1 s
10.27 RO2 source Selects a drive signal to be connected to relay output RO2.
For the available selections, see parameter 10.24 RO1
source.
Running
(95.20 b3)
10.28 RO2 ON delay Defines the activation delay for relay output RO2. 0.0 s
(95.20 b3)
t
On
= 10.28 RO2 ON delay
t
Off
= 10.29 RO2 OFF delay
0.0 3000.0 s Activation delay for RO2. 10 = 1 s
10.29 RO2 OFF delay Defines the deactivation delay for relay output RO2. See
parameter 10.28 RO2 ON delay.
0.0 s
(95.20 b3)
0.0 3000.0 s Deactivation delay for RO2. 10 = 1 s
10.30 RO3 source Selects a drive signal to be connected to relay output RO3.
For the available selections, see parameter 10.24 RO1
source.
Fault (-1)
10.31 RO3 ON delay Defines the activation delay for relay output RO3. 0.0 s
t
On
= 10.31 RO3 ON delay
t
Off
= 10.32 RO3 OFF delay
0.0 3000.0 s Activation delay for RO3. 10 = 1 s
10.32 RO3 OFF delay Defines the deactivation delay for relay output RO3. See
parameter 10.31 RO3 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for RO3. 10 = 1 s
10.51 DI filter time Defines a filtering time for parameters 10.01 DI status and
10.02 DI delayed status.
10.0 ms
0.3 100.0 ms Filtering time for 10.01 and 10.02. 10 = 1 ms
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time