398 Parameters
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
Other [bit] Source selection (see Terms and abbreviations on page 114). -
91
91 Encoder module
settings
Configuration of encoder interface modules.
91.01 FEN DI status Displays the status of the digital inputs of FEN-xx encoder
interface modules.
This parameter is read-only.
-
0000 0000b …
0011 0011b
Status word of digital inputs on FEN-xx modules. 1 = 1
91.02 Module 1 status Displays the type of the interface module found in the location
specified by parameter 91.12 Module 1 location.
This parameter is read-only.
-
No option No module detected in the specified slot. 0
No communication A module has been detected but cannot be communicated
with.
1
Unknown The module type is unknown. 2
FEN-01 An FEN-01 module has been detected and is active. 16
FEN-11 An FEN-11 module has been detected and is active. 17
FEN-21 An FEN-21 module has been detected and is active. 18
FEN-31 An FEN-31 module has been detected and is active. 21
FSE-31 An FSE-31 module has been detected and is active. 25
91.03 Module 2 status Displays the type of the interface module found in the location
specified by parameter 91.14 Module 2 location.
For the indications, see parameter 91.02 Module 1 status.
This parameter is read-only.
-
91.04 Module 1
temperature
Displays the temperature measured through the sensor input
of interface module 1. The unit is selected by parameter 96.16
Unit selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
-
0…1000 °C, °F or
ohm
Temperature measured through interface module 1. -
No. Name/Value Description Def/FbEq16
Bit Name Information
0 DI1 /module 1 DI1 of interface module 1 (see parameters 91.11 and 91.12)
1 DI2 /module 1 DI2 of interface module 1 (see parameters 91.11 and 91.12)
2…3 Reserved
4 DI1 /module 2 DI1 of interface module 2 (see parameters 91.13 and 91.14)
5 DI2 /module 2 DI2 of interface module 2 (see parameters 91.13 and 91.14)
6…15 Reserved